Bac-8001 draft222_14, Connecting inputs – Titus Alpha BAC-8001/BAC-8201 Cooling Only User Manual

Page 11

Advertising
background image

Installing the controllers

Connecting inputs

11

Connecting

inputs

The BAC-8001 and BAC-8201 controllers have preconfigured analog inputs to
support the supplied programs. The inputs cannot be changed to binary or
accumulator inputs. Only one input has an externally available physical
terminal. All of the inputs are preconfigured for the application programs
supplied in the controllers and are listed in Table 2-1.

Discharge air temperature Connect a 10k , Type 3 thermistor temperature probe
to the discharge air temperature input. The input includes the internal pull-up
resistor. An STE-1405 sensor is suitable for this application. Follow the
instructions supplied with the sensor for installation. See

Setting temperature

setpoints on page 30

for setting up discharge air temperature limiting that requires

this input sensor.

Space Temperature Input The space temperature input is connected only
through the RJ-45 thermostat and sensor input jack. It is a configured as an
analog input for STE-6010, STE-6014, and STE-6017 sensors. If an STE-8000
sensor is connected to the controller, this input is ignored. See

Connecting to

sensors on page 15

.

Space Setpoint The space setpoint input is connected only through the RJ-45
thermostat and sensor input jack. It is a configured for the setpoint dials on
STE-6014 or STE-6017 sensors. If an STE-6010 or STE-8000 sensor is connected to
the controller, this input is ignored. See

Connecting to sensors on page 15

.

Primary Duct Pressure The primary duct pressure input is an internal
measurement from the airflow sensor.

Primary Damper Position (BAC-8201 only) The primary damper position input
is preconfigured as an analog input that represents the position of the internal
damper.

Table 2-1 BAC-8001 and BAC-8201 input objects

Object Function

Name

Unit Location

Pull up

AI1

Discharge Air Temperature DISCHARGE AIR

°F

Terminal block

10k

AI2

Space Sensor

SPACE SENSOR

°F

RJ-45

10k

AI3

Space Setpoint

SPACE SETPOINT

°F

RJ-45

10k

AI4

Primary Duct Pressure

PRIMARY DUCT

wc

Internal airflow sensor

N/A

AI5

Primary Damper Position

PRIMARY POSITION Volts Internal damper position N/A

Illustration 2-3 Discharge air temperature