Setting up VAV controllers

Setting temperature setpoints

20

Setting

temperature

setpoints

The space temperate setpoints listed in Table 3-1, “Temperature setpoints,” on
page 24 are used to control the controller VAV operation. The temperature
setpoints have default values, but may be manipulated depending on which
type of wall sensor is connected to the controller.

Occupied cooling and heating setpoints These setpoints are user controlled
space setpoints that originate from an attached sensor. If no sensor is attached
the values for these setpoints are manually entered by a controls technician.

Unoccupied cooling and heating setpoints The unoccupied setpoints are
manually entered values to set the heating and cooling temperature when the
space is unoccupied.

Minimum cooling setpoint A manually entered value to limit the occupied
cooling setpoint regardless of the value entered by the user.

Maximum heating setpoint A manually entered value to limit the occupied
heating setpoint regardless of the value entered by the user.
Minimum setpoint differential Sets the minimum temperature separation
between occupied heating and cooling setpoints.

Standby differential This differential is added or subtracted from the occupied
temperature setpoints to calculate the standby setpoints.

SAT changeover temperature Sets the supply air temperature at which the
controller will change from heating to cooling. The changeover takes place when
the supply air temperature is 2° above or below the discharge air temperature
setpoint.

Table 3-1 Temperature setpoints

Object

Description

Name

Default

AV5

Occupied Cooling Setpoint

OCC CL STPT

74°F

AV6

Occupied Heating Setpoint

OCC HT SPT

70°F

AV7

Unoccupied Cooling Setpoint

UNOCC CL STPT

80°F

AV8

Unoccupied Heating Setpt

UNOCC HT STPT

64°F

AV9

Minimum Cooling Setpt

MIN CL STPT

70°F

AV10

Maximum Heating Setpoint

MAX HT STPT

76°F

AV11

Minimum Setpoint Differential

MIN STPT DIFF

4°F

AV12

Standby Differential

STBY DIFF

3°F

AV37

SAT Changeover Temp

SAT CHANGEOVER

75°F