Connecting

power

The controllers require an external, 24 volt, AC power source. Use the following
guidelines when choosing and wiring transformers.

.

Do not run 24 volt, AC power from within an enclosure to external

controllers.

Connect the 24 volt AC power supply to the power terminal block on the lower
right side of the controller near the power jumper. Connect the ground side of
the transformer to the ground terminal and the AC phase to the phase ~
terminal. Power is applied to the controller when the transformer is powered.

Illustration 2-10 Power terminals and jumper

Illustration 2-11 Power connections

Power

terminals

Use a Titus Alpha Controls Class-2 transformer of the appropriate size to supply

power to the controllers. Titus recommends powering only one controller from each

transformer.