BAC-8001 and BAC-8201 VAV Controllers

Installing the controllers

Connecting outputs

12

Connecting

outputs

The BAC-8001 and BAC-8201 controllers have two preconfigured outputs to
support the supplied programs. The outputs are programmed run the integrated
actuator in either a clockwise or counterclockwise direction. No external output
connections are available.

Connecting to

sensors

Connect any of the following sensors to the RJ-45 thermostat and sensor jack.

STE-8001

STE-8201

STE-6010

STE-6014

STE-6017

Link the controller to sensors with standard straight-through Ethernet cables up
to 75 feet long. See the installation guide supplied with the sensors for complete
sensor installation instructions.

No programming or configuration is required for the supported sensors. The
controller is configured to automatically detect which type of sensor is
connected to it.

Table 2-2 BAC-8001 and BAC-8201output objects

Object Function

Name

False

value

True value

Default

value

Type

BO1

Damper Clockwise

DAMPER CW

Neutral

Clockwise

Neutral

Internal

BO2

Damper Counter

Clockwise

DAMPER CCW

Neutral

Counterclockwise Neutral

Internal

Illustration 2-4 Connecting to a sensor

Maximum 75 feet v

Sensor jack