About the controllers

Specifications

4

Communications

BACnet MS/TP

EIA–485 operating at rates up to 76.8 kilobaud.

Removable screw terminal block.

Wire size 12–24 AWG

Sensor jack

RJ-45 jack compatible with model STE-8000 and

STE-6000 models with RJ-45 jacks

Supported objects

See PIC statement for supported BACnet objects

Control Basic

5 program areas in BAC-8001

6 program areas in BAC-8201

PID loop objects

2

Value objects

60 analog, 32 binary, and 12 multistate

Memory

Programs and program parameters are stored in

nonvolatile memory.

Auto restart on power failure

Application programs

Cooling and heating VAV

Balancing

UL 864 smoke controll (BAC-8201 only)

Air flow sensor features

Configured as BACnet analog input object.

CMOS differential pressure 0-2 inches of water

(0-500 Pa) measurement range. Internally

linearized and temperature compensated.

Span accuracy 4.5% of reading.

Barbed connections for 1/4 FR tubing.

Range dependent upon DP pickup, tubing size/

length and connections.

Actuator specifications

Torque

40 in-lb. (4.5 N

m)

Angular rotation

0 to 95°

Adjustable end stops at 45° and 60° rotation

Motor timing,

BAC-8001 90 sec./90° at 60 Hz

108 sec./90° at 50 Hz

Motor timing,

BAC-8201 60sec./90° at 60 Hz

72 sec./90° at 50 Hz

Shaft size

Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm)

round or 3/8 to 7/16 inch (9.5 to 11 mm) square

damper shafts.

Titus Alpha Controls supplies models BAC-8001

and BAC-8201 with programming sequences for

single-duct VAV applications.