End of life - not recommended for new designs, Specifications – Vicor Autoranging MegaPAC AC-DC Switcher User Manual

Page 20

Advertising
background image

UG:106

vicorpower.com

Applications Engineering: 800 927.9474

Page 20

Input Characterisitcs

Input Voltage

115-230 Vac, 1 Phase, 90-132 Vac, 180-264 Vac, (47-500 Hz) 260-352 Vdc

Power Factor (passive)

0.65

Inrush Current

30A rms @ 115 Vac
60A rms @ 230 Vac

Ride Through Time

>20 ms at nominal line, full load

Power Fail

>3 ms warning

Conducted EMI (47-63 Hz) EN55022 Level A

Surge Immunity

(Common

Mode and Normal Mode)

EN 61000-4-5 Class 3
(Temporary loss of output power may occur which is self recoverable)

Dielectric Withstand

Primary to Chassis GND = 2,121 Vdc
Primary to Secondary = 4,242 Vdc
Secondary to Chassis GND = 750 Vdc

Ouput Characterisitcs

Line/Load Regulation*

0.2% max. from 10% to 100% load
0.5% max. from 0% to 10% load

Setpoint Accuracy

1% for standard voltages
2% for special, adjustable voltages or 48 Vdc

Ripple and Noise

Std. outputs: 2% or 100 mV p-p, whichever is greater, 75% min. load;
VXI options: 50 mV p-p for output voltages <15 Vdc; 150 mV p-p for
output voltages > 15 V and up to and including 24 V; 1% maximum for output
voltages > 24 V. (VXI requires 15% minimum load)
RAMPAC: 10 mVp-p max.or 0.15% whichever is greater
FlexPAC: Mets VXI requirement over total output range

Output Trim Range

50% -110% of nominal voltage VI-200/VI-J00 modules
90% -110% of nominal voltage VI-200/VI-J00 modules 10-15 V
2 V - 25V FlexPACs

Overcurrent Trip Point

105-125% of full load capability of VI-200/VI-J00 modules
Dependent on voltage set for FlexPAC - contact factory

Overvoltage Protection

ModuPACs: 115- 135%; FlexPACs 125% set voltage

Efficiency

Up to 82% typical

Output Power

1,600 W at at 230 Vac;
1,200 W at at 115 Vac

Environmental Characteristics

Storage Temperature

-40°C to +85°C

Operating Temperature**

-20°C to +45°C full power, -20°C to +65°C half power

Humidity

0-95% non-condensing

Altitude

Derate 2.6% total output power for each 1,000 ft to a maximum operating
altitude of 15,000 ft. Non-operating storage maximum altitude is 40 K

Safety Approvals

cURus – UL 60950-1, CSA 60950-1
cTUVus – EN 60950-1, UL 60950-1, CSA 60950-1
CE Mark – Low Voltage Directive, 73/23/EEC amended by 93/68/EEC

Product Weights

9.0 lbs. (4,08 kg) fully configured
0.7 lbs. (0,32 kg) ConverterPAC

Warranty

2 years limited warranty.
See

vicorpower.com

for complete warranty statement.

* See Vicor module specifications. A preload may be necessary for modules trimmed down below

90% of normal output voltage.

** The maximum operating temperature is 45°C. If one is using a VI-200 with output voltage less than

12 V and more than 150 Watts, the operating temperature decreases to 40°C.

Specifications

End of Life - Not Recommended for New Designs

Advertising