Vicor Westcor PFC Mini Power Factor Corrected AC-DC Switcher User Manual
Page 23

UG:115
vicorpower.com
Applications Engineering: 800 927.9474
Page 23
Maxi, Mini, Micro Series Modules (Maxi and Mini Modules Only)
Parameter
MIN
TYP
MAX
UNITS
Notes
Setpoint Accuracy
[d]
Load Regulation
±0.5
±0.1
±1
% of Vnom
% of Vnom
See module design guide
for exact specifications
Temperature Regulation
0.002
0.005
%/°C
-20°C to 100°C
Long Term Drift
Output Ripple & Noise:
≤10 V out
>10 V out
100
1.0
mV
% Vout
20 MHz bandwidth
20 MHz bandwidth
Voltage Trim Range
Maxi/Mini Slots
10-110
% Vout
Preload may be required
Total Remote Sense
Compensation
0.5
Volts
Autosense.
See Pages 8 & 14
OVP Set Point
112
135
% Vout
Recycle Power
Current Limit
115
135
% of I max
Auto Recovery
Overtemperature Limiting
100
115
MMM OTL is non-latching
[d]
For special, adjustable voltages and 48 Vdc outputs, maximum setpoint accuracy is 2% of Vnom.
Note: See individual module data sheets for specific module specifications.