Total and rate display settings and scaling
Total decimal
point

tot_dp=

1234.5

Introduces total decimal point
Demo, e.g., total shown to one decimal place

-

Shift

-

Shift

Next

Accept

Rate decimal
point

tot_dp=

12.345

Introduces rate decimal point
Demo, e.g., rate shown to 3 decimal places

-

Shift

-

Shift

Next

Accept

Rate scaling
factor

rATE=_SF=

1000

Introduces rate scaling factor
e.g., 1000 rate units = 1 total unit

-

Dec

-

Inc

Next

Accept

Rate timebase

rate_SEC

rate_min

rate_Hr

Rate is in units per second
Rate is in units per minute
Rate is in units per hour

Toggle

Accept

Number of
samples

SAmp=

10

Introduces the number of samples used for
rate, e.g., 10

-

Dec

-

Inc

Next

Accept

Show rate or
total

dis=rate

dis=tot

Display normally shows the rate
Display normally shows the total

Toggle

Accept

Reset key enable
Reset Total Key
Enable

En_resY

En_resn

RESET key resets count
RESET key ignored

Toggle

Accept

Alarm enable
Alarms 1 & 2
Select

A12Y

A12n

Enable
Disable (Select this option for PMX420)

Toggle

Accept

Alarm channel one settings
Coil energisa-
tion

A1_nor_E

A1_nor_d

Normally energised
Normally de-energised

Toggle

Accept

Alarm one type

A1=_rate

A1=_tot_

Channel one monitors total
Channel one monitors rate

Toggle

Accept

Alarm one
action

A1=_LO

A1=_HI

Low type (active below setpoint)
High type (active above setpoint)

Toggle

Accept

Setpoint value

Set_Pt1=

50.00

Setpoint value
e.g., 50.00 %

-

Dec

-

Inc

Next

Accept

Deadband
value

dband_1=

0.01

Deadband value
e.g., 0.01 %

-

Dec

-

Inc

Next

Accept

Timer delay

delay_1=

20

Timer delay (set to 0 s to disable)
e.g., 20 s

-

Dec

-

Inc

Next

Accept

Alarm channel two settings
As above

As channel one (except uses

A2_nor_E, A2=_rate,..., delay_2=)

Setup Sequence (continued)