Weidmuller PTX800D - Scalable pulse and frequency counter User Manual

Page 14

Advertising
background image

6

Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Strip wires to  mm from the ends. Use a suitable ferrule for
multistranded wires (do not solder).

Pin

Signal

1

Neutral / –

Power supply

2

Live / +

3

Signal +

Analogue output (optional)

4

Signal –

5

0V

Pulse output

6

Pulse

7

Reset count

Short to 12 to reset

8

Security

Short to 12 for setup mode

9

Pull Up/Down

Inputs

10

Input – / 0 V

11

Input +

12

+12 V DC (out)

13

Normally Closed

Alarm one
(optional)

14

Common

15

Normally Open

16

Normally Closed

Alarm two
(optional)

17

Common

18

Normally Open

Input signals
The PTX800D input circuits are rated category II (suitable for
measurements performed on the low voltage installation). They may
safely be floating with respect to local ground (i.e., subject to common
mode voltages) up to 50 V DC.