Mounting Instructions

This unit can be mounted on a DIN rail either using the mounting
brackets on the back or four screws through the holes on the tabs
extending from the corners of the housing. In order to reduce the
influences of electromagnetic disturbances, ensure that none of
the connecting cables are lying next to high power or high
frequency circuit cables.

Electrical Configuration

The controller unit contains a main PCB that controls light array
electronics, as well as an extension PCB for additional
I/O or communication functionality (model dependent). The
emitter and receiver light arrays must be connected to the
controller through their respective RJ45 connectors on the main
PCB. The grommets (provided) should be installed in the gaps on
the side of the controller around the electrical cables. After
connecting the cable and placing the grommets, mount the clear
plastic cover using the screws provided.

Figure 1: Controller

This main board has two digital inputs and two digital outputs as
well as power connections on the terminal connector. The pin
descriptions for this connector are listed in Table 1. Any additional
connections to be made to the extension PCB are detailed in the
model specific sections of this document.

The cables must be mounted using the
provided grommets in order to maintain IP54
standards.

Do not allow the cables to be pinched or
mechanically stressed in the mounted
environment.

ATTENTION

For use in NFPA 79 applications only.

IMPORTANT

In 2

PNP

NPN

PNP

NPN

D7 LED - Power

Model Specific

Extension PCB

D3 LED Out 1
D4 LED Out 2
D6 LED In 2
D5 LED In 1

RJ45 Connector
Emitter

RJ45 Connector
Receiver

D2 LED
D1 LED

Gaps

for

cables

Out 1

In 1

Out 2
In 1
In 2
n. c.
Earth.
24 VDC
0 VDC

Pot 2

Pot 1

Removable

Spring-Loaded

Connector

Input
Logic
Jumpers

S1

J2

J14

Table 1: Controller Terminal Connector Pin Allocation

Functional Description All Models

Response Time

The measurement or response time (T) can be roughly calculated
from the number of beams (n), the scan time per beam (t

S

) and

the analysis time (t

A

):

T = t

A

+ n x t

S

n = number of optical beams

For t

S

and t

A

the following approximate values can be assumed:

Table 2: Response Time Details

 Double-scan mode can be set with the DIP switches on these models.

For example, for a 600 mm array with a 10 mm beam spacing
utilizing the I/O model controller, the response time is calculated
as follows:

T = 5.3 + 60 x 0.275 = 21.8 ms

Pin

Signal

Description

1

0V DC

Power

2

+24V DC

Power

3

Ground

Ground

4

Not connected

Not connected

5

In 2

Model specific descriptions

6

In 1

7

Out 2

8

Out 1

Model

t

A

(ms) ± 5%

t

S

(ms) ± 5%

45MLA-CTRL-ALG single scan mode (default)

4.1

0.13

45MLA-CTRL-ALG double scan mode

4.1

0.25

45MLA-CTRL-BSC single scan mode (default)

0.6

0.14

45MLA-CTRL-BSC double scan mode

0.8

0.25

45MLA-CTRL

5.3

0.275

45MLA-CTRL-485

2.1

0.275

45MLA-CTRL-CAN

1.0

0.275

The ground connection of the 45 MLA and
controller systems can be made either at the
light arrays or the controller. Do not ground
both the arrays and the controller as that may
create ground loops.

ATTENTION