No. parameter min/max display/options default – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 20

Advertising
background image

English-20

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

T064 [Relay 2 Off Time]

0.0/600.0 Secs

0.1 Secs

0.0 Secs

T065 [Opto Out Sel]

0/17

0 = “Ready/Fault”
1 = “At Frequency”
2 = “MotorRunning”
3 = “Hand Active”
4 = “Motor Overld”
5 = “Ramp Reg”
6 = “Above Freq”
7 = “Above Cur”
8 = “Above DCVolt”

9 = “Above Anlg 2”
10 = “Above PF Anlg”
11 = “Anlg In Loss”
12 = “ParamControl”
13 = “Retries Exst”
14 = “NonRec Fault”
15 = “Reverse”
16 = “Logic In 1”
17 = “Logic In 2”

1

T066 [Opto Out Level]

0.0/9999

0.1

0.0

T068 [Opto Out Logic]

0/1

1

0

T069 [Analog In 1 Sel]

0/6

1

2

T070
T074

[Analog In 1 Lo]
[Analog In 2 Lo]

0.0/100.0%

0.1%

0.0%

T071
T075

[Analog In 1 Hi]
[Analog in 2 Hi]

0.0/100.0%

0.1%

100.0%

T072
T076

[Analog In 1 Loss]
[Analog In 2 Loss]

0/6

0 = “Disabled”
1 = “Fault (F29)”
2 = “Stop”

3 = “Zero Ref”
4 = “Min Freq Ref”
5 = “Max Freq Ref”
6 = “Int Freq Ref”

0

T073 [Analog In 2 Sel]

0/7

1

2

T077 [Sleep-Wake Sel]

0/3

0 = “Disabled”
1 = “Analog In 1”

2 = “Analog In 2”
3 = “Command Freq”

0

T078 [Sleep Level]

0.0/100.0%

0.1%

10.0%

T079 [Sleep Time]

0.0/600.0 Secs

0.1 Secs

0.0 Secs

T080 [Wake Level]

0.0/100.0%

0.1%

15.0%

T081 [Wake Time]

0.0/600.0 Secs

0.1 Secs

0.0 Secs

No.

Parameter

Min/Max

Display/Options

Default

T065 Setting

T066 Min/Max

6

0/400 Hz

7

0/180%

8

0/815 Volts

9

0/100%

10

1/180 degs

12

0/1

T068 Option

Opto Out Logic

0

NO (Normally Open)

1

NC (Normally Closed)

T069 Option

Setting

Input Range

DIP Switch AI1 Setting

0

Current Mode

0-20 mA

0-10V

1

Current Mode

4-20 mA

0-10V

2

Voltage Mode - Unipolar

0-10V

0-10V

4

Current Mode (Square Root)

0-20 mA

0-10V

5

Current Mode (Square Root)

4-20 mA

0-10V

6

Voltage Mode - Unipolar (Square Root)

0-10V

0-20 mA

T073 Option

Setting

Input Range

DIP Switch AI1 Setting

0

Current Mode

0-20 mA

20 mA

1

Current Mode

4-20 mA

20 mA

2

Voltage Mode - Unipolar

0-10V

10V

3

Voltage Mode - Bipolar

-10 to +10V

10V

4

Current Mode (Square Root)

0-20 mA

20 mA

5

Current Mode (Square Root)

4-20 mA

20 mA

6

Voltage Mode - Unipolar (Square Root)

0-10V

10V

7

Voltage Mode - Bipolar (Square Root)

-10 to +10V

10V