Advanced program group parameters – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 22

Advertising
background image

English-22

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Advanced Program Group Parameters

No.

Parameter

Min/Max

Display/Options

Default

A141 [Purge Frequency]

0.0/320.0 Hz

0.1 Hz

5.0 Hz

A142 [Internal Freq]

0.00/320.00 Hz

0.01 Hz

60.00 Hz

A143
A144
A145
A146

[Preset Freq 0]
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]

0.0/320.0 Hz

0.1 Hz

0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz

A147 [Accel Time 2]

0.00/600.00 Secs

0.01 Secs

30.00 Secs

A148 [Decel Time 2]

0.00/600.00 Secs

0.01 Secs

30.00 Secs

A149 [S Curve %]

0/100%

1%

20%

A150 [PID Trim Hi]

0.0/320.0 Hz

0.1 Hz

60.0 Hz

A151 [PID Trim Lo]

0.0/320.0 Hz

0.1 Hz

0.0 Hz

A152 [PID Ref Sel]

0/8

0 = “PID Disabled”
1 = “PID Setpoint”
2 = “Analog In 1”
3 = “Analog In 2”

4 = “Comm Port”
5 = “Setpnt, Trim”
6 = “A-In 1, Trim”
7 = “A-In 2, Trim”
8 = “Comm, Trim”

0

A153 [PID Feedback Sel]

0/2

0 = “Analog In 1”
1 = “Analog In 2”

2 = “Comm Port”

0

A154 [PID Prop Gain]

0.00/99.99

0.01

1.00

A155 [PID Integ Time]

0.0/999.9 Secs

0.1 Secs

2.0 Secs

A156 [PID Diff Rate]

0.00/99.99 (1/Secs)

0.01 (1/Secs)

0.00 (1/Secs)

A157 [PID Setpoint]

0.0/100.0%

0.1%

0.0%

A158 [PID Deadband]

0.0/10.0%

0.1%

0.0%

A159 [PID Preload]

0.0/320.0 Hz

0.1 Hz

0.0%

A160 [Process Factor]

0.1/999.9

0.1

30.0

A163 [Auto Rstrt Tries]

0/9

1

0

A164 [Auto Rstrt Delay]

0.0/160.0 Secs

0.1 Secs

1.0 Secs

A165 [Start At PowerUp]

0/1

0 = “Disabled”

1 = “Enabled”

0

A166 [Reverse Disable]

0/1

0 = “Rev Enabled”

1 = “Rev Disabled”

1

A167 [Flying Start En]

0/1

0 = “Disabled”

1 = “Enabled”

0

A168 [PWM Frequency]

2.0/8.0, 10.0 kHz

0.1 kHz

4.0 kHz

A169 [PWM Mode]

0/1

0 = “Space Vector”

1 = “2-Phase”

1

A170 [Boost Select]

0/15

Settings in % of base voltage.

4

Only active when A125 [Torque Perf Mode] is
set to 0 “V/Hz”.

0 = “Custom V/Hz”
Variable Torque

Constant Torque

1 = “30.0, VT”

5 = “0.0, no IR”

10 = “10.0, CT”

2 = “35.0, VT”

6 = “0.0”

11 = “12.5, CT”

3 = “40.0, VT”

7 = “2.5, CT”

12 = “15.0, CT”

4 = “45.0, VT”

8 = “5.0, CT”

13 = “17.5, CT”

9 = “7.5, CT”

14 = “20.0, CT”
15 = “Kepco”

A171 [Start Boost]

0.0/25.0%

1.1%

2.5%

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.

A172 [Break Voltage]

0.0/100.0%

0.1%

25.0%

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.

A173 [Break Frequency]

0.0/320.0 Hz

0.1 Hz

15.0 Hz

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.

A174 [Maximum Voltage]

20/Rated Volts

1 VAC

Rated Volts

A175 [Slip Hertz @ FLA]

0.0/10.0 Hz

0.1 Hz

2.0 Hz

A176 [DC Brake Time]

0.0/99.9 Secs

0.1 Secs

0.0 Secs

A177 [DC Brake Level]

0.0/(Drive Amps

×

1.5) 0.1 Amps

Amps

×

0.05

A178 [DC Brk Time@Strt]

0.0/99.9 Secs

0.1 Secs

0.0 Secs

A179
A180

[Current Limit 1]
[Current Limit 2]

0.0/(Drive Amps

×

1.5) 0.1 Amps

Amps

×

1.1

A181 [Motor OL Select]

0/2

0 = “No Derate”

1 = “Min Derate”
2 = “Max Derate”

0