Power wiring – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual
Page 7

PowerFlex 400 Adjustable Frequency AC Drive Quick Start
English-7
Figure 3: Power Terminal Blocks
Power Wiring
Terminal
(1)
Description
R/L1, S/L2, T/L3 3-Phase Input
U/T1
To Motor U/T1
=
Switch any two motor
leads to change
forward direction.
V/T2
To Motor V/T2
W/T3
To Motor W/T3
P2, P1
DC Bus Inductor Connection
Drives are shipped with a jumper between Terminals
P2 and P1. Remove this jumper only when a DC Bus
Inductor will be connected. Drive will not power up
without a jumper or inductor connected.
DC–, DC+
DC Bus Connection (Frame C Drives)
P2, DC–
DC Bus Connection (Frame D, E, and F Drives)
BR+, BR–
Not Used
Safety Ground - PE
(1)
Important: Terminal screws may become loose during shipment. Ensure that all
terminal screws are tightened to the recommended torque before applying power to
the drive.
R/L1 S/L2 T/L3
P1
P2
DC– U/T1 V/T2 W/T3
R/L1 S/L2 T/L3 P1
P2
DC– U/T1 V/T2 W/T3
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 P2
P1
BR–
BR+
DC+
DC–
R/L1S/L2T/L3
P1 P2 DC–
U/T1V/T2W/T3
R/L1 S/L2 T/L3 P1
P2 DC–
U/T1 V/T2 W/T3