6 ColorSight Series 9000 PHOTOSWITCH

R

Photoelectric Sensor

75027--031--01(A), November 1999

Dip-Switches

A bank of 6 dip-switches are provided for configuring various operating

modes and parameters available with ColorSight. These are defined in the

table below and explained in further detail in the Configuration section on

page 10.

Switch

Label

Function

Switch Up

Switch Down

S1

None

Not used

S2

 / =

Select target match/no match

Output inactive

Output active 

S3

TD/0

Enable/disable time delay

50ms time delay active

No time delay 

S4

CI/C

Select color + intensity

mode/color only mode

Color + intensity mode

active 

Color only mode active

S5

SG/AV

Select single/average mode

Single sample mode

active

Average sample mode

active 

S6

GT/LRN Select gate/remote learn mode

Input functions as gating

input

Input functions as remote

learn 

Factory default

Indicators

Three LED indicators are provided to indicate a variety of conditions

making it easy for installation and troubleshooting. The function of each is

described in the table below.

Label

Color

State

Condition

PWR

Green

OFF

Sensor power not present

Steady

Sensor power present

OUTPUT/LEARN

Yellow

OFF

Output inactive

Steady

Output active

Flash

Learn mode activated

FAULT/SCP

Red

OFF

Sensor operating normally 

Steady

Marginal detection of target 

Flash

Output SCP active

LED also OFF when LEARN pushbutton depressed.

Includes failure to learn color during LEARN process.