42CRC Color Registration Control

After the control has been properly installed and the chosen operating

mode has been selected, set the dwell and the sensitivity controls to the full

counter-clockwise position. Apply power to the control and set the web in

motion. THE WEB MUST BE MOVING AT LEAST 2 INCHES (51 mm)

PER SECOND FOR PROPER CONTROL FUNCTION.

Automatic, Non-Latch

In this setting no sensitivity adjustment is required and the sensitivity

control is inoperative. Set the dwell control to the desired output dwell by

rotating the adjustment clockwise to increase the time to a maximum of

250 milliseconds.

Automatic, Latch

No sensitivity or dwell time adjustments are required and both controls are

inoperative.

Manual, Non-Latch

Rotate the sensitivity control clockwise until the “Green Margin Light”

illuminates with the presence of a moving mark. This setting provides the

correct signal for reliable operation. If output dwell time is required, rotate

the dwell control clockwise to the appropriate duration.

Manual, Latch

Set the sensitivity control as described above. The dwell time is

inoperative.

Gating

FIGURE 9

LIGHT MARK

DARK MARK

WEB

MATERIAL

42CRC-4000

NPN OUTPUT

NO-GATING

42CRC-4001

NPN OUTPUT

GATED

42CRC-4001

PNP OUTPUT

GATED

42CRC-4001

PNP OUTPUT

NO-GATING

GATING

SIGNAL

X Y

X Y

X Y