Coolant requirements, General cooling system requirements – Rockwell Automation 20GY PowerFlex 755 with OEM Liquid Cooling Frame 6 and 7 AC Drives User Manual

Page 8

Advertising
background image

Rockwell Automation Publication 20GY-IN001A-EN-P - June 2011

8

PowerFlex® 755 with OEM Liquid Cooling Frame 6 and 7 AC Drives

Coolant Requirements

General Cooling System Requirements

Table 1

lists the required coolant specifications for PowerFlex 755 with OEM

Liquid Cooling Frame 6 and 7 AC drives.

Table 1 - Required Coolant Specifications

Non-diluted coolants require a coolant-to-water mix ratio of 50% by volume.

Specification

Description

Maximum Rated Pressure

1275 kPa (185 psig)

Minimum Flow Rate

19 liters/min (5 gal/min)

Coolant Temperature

0…46 °C (32…115 °F )

Coolant Fitting Type

Brass #10 o-ring face seal

Coolant Fitting Torque

81 N•m (60 lb•ft ) ±10%

Coolant Specification

Description

OEM-specific coolants are
qualified

Consult factory for details

Water-Glycol Coolants:

Interstate Chemical
www.interstatechemical.com/
contact.htm

Use only approved coolant (consult factory for details)
NFP-50

(1)

; a 50/50 premix of propylene glycol and distilled water

NFE-50

(1)

; a 50/50 premix of ethylene glycol and distilled water

(1) Available in 5 gallon pails.

Koolant Koolers/Dimplex
Thermal Solutions
www.koolantkoolers.com/
index.php/nic=contact

K-Kool-E

(1)

; ethylene glycol (available premixed with distilled

water)

Propylene gylcol

(1)

also available

Dow Chemical
www.dow.com

Dowtherm

®

SR-1

(2)

; ethylene glycol

Dowfrost

®

(2)

; propylene glycol

Dowtherm and Dowfrost are registered trademarks of Dow Chemical Co.

(2) Not premixed with distilled water, and may not be available in 5 gallon quantities.

IMPORTANT

Since coolant performance slowly degrades over time, the drive loop
coolant should be replaced every two years and/or whenever the loop
is drained for servicing.

Advertising