Rockwell Automation 42DBS-5100 Background Suppression with Timing PHOTOSWITCH User Manual

Page 2

Advertising
background image

22

OPERATING MARGIN

1. The operating margin is parenthesis are for diffuse white surfaces

that fill the control’s field of view.

2. 6.1% and 2.6% designate dark colored surfaces having diffuse re-

flectance of 6.1% and 2.6% respectively compared to diffuse white.

3. The 2.6% surface is Krylon # 1602 Ultra flat black.

TYPICAL SUPPRESSION CURVE

DIST

AN

CE

TO

SE

NSE

D

OB

JEC

T

DISTANCE TO BACKGROUND OBJECT

14

(35.5cm)

12

(30.5cm)

10

(25.4cm)

8

(20.3cm)

6

(15.2cm)

4

(10.1cm)

2

(5.08cm)

0

0

2

(5.08cm)

4

(10.1cm)

6

(15.2cm)

8

(20.3cm)

10

(25.4cm)

12

(30.5cm)

14

(35.5cm)

(O

PERA

TING
M

ARGI

N)

M

-16

(O

PER
AT

IN

G

M

AR

GI

N)

M

-38

WHITE PAPER

6.1%

2.6%

TYPICAL RESPONSE CURVE

OPE

RA

TIN

G

M

AR

GIN

OPERATING DISTANCE

100X

10X

.1”

(.254cm)

1000x

1X

.3”

(.762cm)

.5”

(1.27cm)

.8”

(2.032cm)

2”

(5.08cm)

4”

(10.16cm)

6”

(15.24cm)

8”

(20.3cm)

10”

(25cm)

12”

(30cm)

SUPPRESSION SET FOR 8(20.3CM)

WIRING

All external wiring should conform to the National Electric Code and

applicable local codes. See wiring diagrams for external connections.

TYPICAL WIRING DIAGRAMS

+

(+)

3

2

1

TTL Logic

--

Black

(--)

TERMINAL BASE

Programmable

Controller

DC Interface

10--30VDC

+5VDC

Blue

Grey

Orange

Red

Floating Shield

CABLE BASE

ALIGNMENT

1. Loosen lock to allow sensing range adjustment.
2. Adjust “Coarse” sensing range adjustment to the maximum posi-

tion (full counterclockwise position)

3. Set “Light Energized” (LT)/“Dark Energized” (DK) switch to the

Light Energized position.

4. Select short (0--1.5sec) or Long (0--15sec) “off delay” (one-shot)

switch.

5. Select short (0--1.5sec) or Long (0--15sec) “on delay” (one-shot)

switch.

6. Select “Time delay” (TD) or “One-Shot” (OS) operation switch .
7. Set the on time to minimum, with the on-timing pot. (full counter

clockwise)

8. Set the off-time to maximum, with the off-timing pot, when in

short-off mode (full clockwise) or to at least 2--3 seconds, when

in long-off mode.

9. Turn “coarse” sensing range adjustment to the minimum position

(full clockwise).

10. Position the control in its application and increase the sensing

range until the control senses the background. The Red LED in-

dicator will turn On. The Green LED (2X margin indicator) will

probably turn On.

11. With the “fine” adjustment, decrease the sensing range until the

Green LED turns Off.

12. Place the object to be detected in front of the control at the ex-

pected sensing distance. Both red and green LED’s should turn

On. Remove the target.

13. Time Delay Operation -- If after the off delay has elapsed the

Red LED indicator turns Off, the control has the correct adjust-

ments and settings should be locked with the lock screw. If

the Red LED does not turn Off, slightly reduce the sensing

range with the fine sensing range adjustment and repeat steps

12 and 13.

14. One-Shot Operation -- Replace the target in front of the control

after the one shot time has elapsed. If the Red LED turns On,

the settings are correct and can be locked with the lock screw.

If the Red LED does not turn On, slightly reduce the sensing

range with the fine sensing range adjustment and repeat steps

12 and 14.