Step 6: Remove the
Existing SCR Modules

1. Remove the two screws and washers that secure each SCR Module to

the heatsink and remove the SCR Modules.

Step 7: Install the New
SCR Modules

Install the new SCR modules in reverse order of removal as detailed in Step
6:

Remove the Existing SCR Modules

above.

Important: Verify that each SCR Module is orientated in the same position

as it was prior to removal.

Important: Thermal grease must be applied to the bottom of the SCR

modules before securing them to the heatsink.

Use the following table to determine the proper tightening torque for the
SCR Modules installed.

=

Regenerative drive

Non-Regenerative drive

Remove screws

Remove screws

230V AC Input

460V AC Input

Part Number

Final Torque

Part Number

Final Torque

SK-20P-S7F46

2.5…4 N•m (22…35.4 lb•in)

SK-20P-S7F75

2.5…4 N•m (22…35.4 lb•in)

SK-20P-S7F47

2.5…4 N•m (22…35.4 lb•in)

SK-20P-S7F77

2.5…4 N•m (22…35.4 lb•in)