5. Remove the appropriate gate leads:
– For regenerative drives, remove each pair of (orange and yellow) gate
lead cables from connectors KG01…KG06 and KG1…KG6 and push 
each lead through the appropriate opening in the board.
– For non-regenerative drives, remove each pair of (orange and yellow)
gate lead cables from connectors KG01…KG06 and push each lead 
through the appropriate opening in the board.
Important: Remove the gate leads by grasping the connector and
pulling up. DO NOT pull the gate leads off by pulling on 
the wires.
6. Remove the cable from connectors XTA on the Pulse Transformer
board.
Remove cable 
from XTA
For regenerative 
drives, remove 12 
gate leads and 
push through holes 
in board
Remove cable 
from XTA
For 
non-regenerative 
drives, remove six 
gate leads and push 
through holes in 
board