Configuring the Communications Adapter

After mounting and connecting the Comms Kit, configure
the communication adapter. Refer to the Communication
Adapter User Manual for complete details.

External Comms Kit Specifications

Communications

Electrical

Mechanical

Environmental

Regulatory Compliance

NOTE: This is a product of category C2 according to IEC
61800-3. In a domestic environment this product may cause
radio interference in which case supplementary mitigation
measures may be required.

24V DC
Power Terminal
Block

(1)

Connection for 24V DC (+15% / -25%) power
source. Connect the “ + ” and “ - ” wires of the
DC power source to the 2-pin linear plug
(provided with Comms Kit), matching the
respective polarity. Then insert the 2-pin linear
plug into the mating DC power terminal block.

NOTE: When powering the Comms Kit with the
accessory 20-XCOMM-AC-PS1 power adapter,
this terminal block can be used to daisy-chain
24V DC to other kits (

Figure 5

).

AC-to-DC
Adapter
Connector

(1)(2)

Connection for AC-to-DC adapter, such as
Allen-Bradley 20-XCOMM-AC-PS1, when not
using a DC power source. Plug the adapter into
the mating DC ADP connector.

DSI Connector

Connection for DSI. Using a 22-RJ45CBL-Cxx
Communications Cable or AK-U0-RJ45-TB2P
Terminal Block Adapter and appropriate twisted
pair cable, connect one end into the mating DSI
connector of the Comms Kit and the other end
into the RJ45 port on the bottom of the drive.

Important: Always make this connection before
configuring the adapter. Also, always set the
connected drive’s parameter A103 - [Comm
Data Rate] to “4” (19.2 K).

RS232 DF1
Port

Connection for PC to use software tools. Using
a 1203-SFC cable, connect one end into the
mating Serial connector of the Comms Kit and
the other end into a PC COM port.

Important: Always make this connection before
configuring the adapter. Also, when establishing
communication between the computer and this
port always set the baud rate to “19.2 K.”

NOTE: This port is not functional on a
22-COMM-L or 22-COMM-P adapter.

(1)

The DC power source or AC-to-DC converter used to power the Comms Kit must
be capable of providing a minimum of 150 mA @ 18…27V DC. Also, its
connector must be of “pin and barrel” construction with a 2mm pin.

(2)

To power additional Comms Kits, see

Powering Daisy-Chained Comms Kits on

page 4

.

Network

Dependent on installed 22-COMM-* adapter

Drive

Protocol
Data Rate

DSI
19.2 kbps

Item Description

Connection Procedure

+

-

Drive

60 mA at 12V DC supplied from drive via DSI cable

Network

None for all network protocols except:

DeviceNet

60 mA at 24V DC

DC Power Supply
Requirement

(1)

(1)

Since the Comms Kit is powered by a nominal 24V DC, the current consumption
listed in this table differs from the value shown on the label of the communication
adapter, which is based on the adapter being powered by 5V DC from the drive.

22-COMM-B

75 mA at 24V DC

22-COMM-C

110 mA at 24V DC

22-COMM-D

60 mA at 24V DC

22-COMM-E

140 mA at 24V DC

22-COMM-L

60 mA at 24V DC

22-COMM-P

60 mA at 24V DC

Dimensions

Width
Height
Depth

108 mm (4.25 in.)
108 mm (4.25 in.) with terminal connector attached
75 mm (2.95 in.)

Weight

340 g (12 oz.)

Temperature

Operating
Storage

-10…50°C (14…122°F)
-40…85°C (-40…185°F)

Relative Humidity

5…95% non-condensing

Atmosphere

Important: The Comms Kit must not be installed in
an area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the
Comms Kit is not going to be installed for a period of
time, it must be stored in an area where it will not be
exposed to a corrosive atmosphere.

Shock

Operational

Non-operational

30g, 11 ms (DIN Rail Mount)
50g, 11 ms (Panel Mount)
30g, 11 ms (DIN Rail Mount)
50g, 11 ms (Panel Mount)

Vibration

Operational
Non-operational

2.5g, 5…2000 Hz
5.0g, 5…2000 Hz

UL

UL508C

cUL

CAN / CSA C22.2 No. 14-M91

CE

EN50178 and EN61800-3

CTick

EN61800-3