Ac power adapter (20-xcomm-ac-ps1), Ac power adapter specifications, Electrical connections – Rockwell Automation 22-XCOMM-DC-BASE DSI External Communications Kit User Manual
Page 4: Powering a single comms kit, Powering daisy-chained comms kits, Figure 5, Powering daisy-chained comms kits on
 
The 20-XCOMM-AC-PS1 is an accessory AC-to-DC 
converter for use with the External Comms Kits. It is used 
when only 100…240V AC power is available inside a 
control panel. The converter, which comes with 
interchangeable plugs, is shown below. The converter 
connects to an AC receptacle inside the control panel. Use 
the appropriate plug for your region: 
AC Power Adapter Specifications
Electrical Connections
Powering a Single Comms Kit
The DC output plug is connected to the mating DC ADP 
connector on the 22-XCOMM-DC-BASE.
Powering Daisy-Chained Comms Kits
Additional Comms Kits can be powered by daisy-chaining 
them together. For each Comms Kit in the chain, connect all 
DC “+” terminals together and all DC “-” terminals together 
(
Figure 5 Powering Multiple Comms Kits via Daisy Chaining
The number of Comms Kits that can be daisy-chained 
together is dependent on:
• Total current consumed by all of the communication
adapters being daisy-chained. For adapter current 
consumptions at 24V DC, see 
.
• Available current output capacity of the AC-to-DC
converter being used.
The following example explains how to determine the 
number of daisy-chained Comms Kits that can be powered:
Example: Suppose the Comms Kits being daisy-chained 
each have an installed 22-COMM-D DeviceNet adapter, and 
that the kits will be powered by the 20-XCOMM-AC-PS1 
converter which has an output capacity of 830 mA.
Since the current consumed by one Comms Kit is 60 mA, 
divide the power source’s available output capacity by this 
consumption (830 mA ÷
60 mA = 13.83), and round down
the result. For this example, up to 13 daisy-chained Comms 
Kits can be powered.
AC Power Adapter (20-XCOMM-AC-PS1)
Input
Rated Input Voltage
Operating Input Voltage
AC Input Frequency
100…240V AC
90…264V AC
47…63 Hz
Output
Output Voltage
Output Current
24V DC
830 mA
TIP: It is highly recommended to use twisted wire 
pairs for better noise immunity.
For use in
the US
For use in
the UK
For use in
Europe
For use in
Australia
DSI External Comms Kits
(22-XCOMM-DC-BASE)
AC-to-DC Converter
(20-XCOMM-AC-PS1)
. . .
+ -
+ -
+ -
+ -
www.rockwellautomation.com
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Power, Control and Information Solutions Headquarters
Publication 22COMM-IN001E-EN-P – February, 2011
PN-105040
Supersedes 22COMM-IN001D-EN-P – July 2007
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in USA.
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives