Installing the Option Module Chapter 2

This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded SpdRef ]. If a
problem occurs, this verification step provides the diagnostic capability to
determine whether the drive/option module or the network is the cause.

4.

If hard-wired discrete digital inputs are not used to control the drive, verify
that all unused digital input drive parameters are set to ‘0’ (Not Used).

Commissioning the Option

Module

To commission the option module, you must set a unique network node address.
See the

Glossary

for details about IP addresses. Also, see

Setting the IP Address

Selection Jumper on page 18

for details on selecting the source (default address,

from a DHCP server, or from option module parameters) for the network
address.

IMPORTANT New settings for some option module parameters (for example Device

Parameters 04 - [IP Addr Cfg 1] through 07 - [IP Addr Cfg 4]) are
recognized only when power is applied to the option module or it is reset.
After you change parameter settings, cycle power or reset the option
module.