Configuring the Option Module Chapter 3

9.

Reset the option module using

Device Parameter 03 - [Reset Module] or

by cycling power to the drive so that the restored parameters take effect.

Viewing the Option Module

Status Using Parameters

The following parameter provides information about the status of the option
module. You can view this parameter at any time.

Updating the Option

Module Firmware

The option module firmware can be updated over the network or serially through
a direct connection from a computer to the drive using a 1203-USB or 1203-SSS
serial converter.

When updating firmware over the network, you can use the Allen-Bradley
ControlFLASH software tool, the built-in update capability of DriveExplorer
Lite or Full software, or the built-in update capability of DriveExecutive software.

When updating firmware through a direct serial connection from a computer to a
drive, you can use the same Allen-Bradley software tools described above, or you
can use HyperTerminal software set to the X-modem protocol.

To obtain a firmware update for this option module, go to

http://www.ab.com/

support/abdrives/webupdate.

This website contains all firmware update files and

associated Release Notes that describe the following items:

• Firmware update enhancements and anomalies
• How to determine the existing firmware revision
• How to update the firmware using ControlFLASH, DriveExplorer, or

DriveExecutive software.

IMPORTANT When performing a Set Defaults, the drive may detect a conflict

and then not allow this function to occur. If this happens, first
resolve the conflict and then repeat this Set Defaults procedure.
Common reasons for a conflict include a drive running or a
controller (master) in Run mode.

Module Device Parameter

Description

02 - [Net Addr Src]

Displays the source from which the option module network address

is taken. It is either ’0’ (Parameters) or ‘1’ (Default) which uses the

following defaults:
IP Address 192.168.0.1

Subnet Mask 255.255.255.0

Gateway Address 192.168.0.1