Adding or changing contact cartridges – Rockwell Automation 700-RTC_RTCR Type RTC RTCR Solid-State Relays User Manual

Page 2

Advertising
background image

Publication 700-IN003C-EN-P - October 2009

2 Bulletin 700 Type RTC & RTCR Solid-State Relays

Adding or Changing
Contact Cartridges

Figure 1. Removing and Orientation of Cartridges

Timers are supplied with two slots for timed contacts and two slots for
instantaneous contacts. “Dummy” cartridges are placed in any unused
cartridge slots to guard against entrance of foreign material.

The N.O. cartridges, N.C. cartridges, and dummy cartridges are removable and
interchangeable using the same cartridges for both timed and instantaneous
slots, with the exception of the N.C. cartridges in the instantaneous positions
(reference Note on page 1) Use the following procedure:

1. Disconnect all power from timer or timer panel.

2. Loosen the two front housing screws (See Figure 1.) until the housing

slides back along the screws for approximately one inch. The screws are
captive and will restrain the front housing to protect the circuit cable
that connects to the timer base.

3. Remove the N.O. or N.C. contact or the dummy cartridge by lifting it

out of the slot. A screwdriver is required to pry out the dummy
cartridge.

Contact Cartridges

Type

Color

Catalog Number

Normally Open

Gray

700-CRT5

Normally Closed

Orange

700-CRT6

Dummy

Black

700-CR9

ATTENTION

The glass envelopes in the N.O. and N.C. cartridges can be
damaged if dropped or mishandled. Damaged cartridges
must be replaced.

Orientation of cartridges

Method of removing cartridge

Projection for Keying

Insert cartridge with this end at top of timer

Advertising