Publication 700-IN003C-EN-P - October 2009

4 Bulletin 700 Type RTC & RTCR Solid-State Relays

Table 1 Timer Operation

Note:

When the timer is energized or times out in the on-delay mode, an

N.O. contact may close before an N.C. contact opens; this can occur because
of inherent operating characteristics. Similarly, when the timer is de-energized
or times out in the off-delay mode, an N.C. contact may close before an N.O.
opens. Assured contact overlap or non-overlap cannot be provided in the same
device.

Terminals

Terminal clamps are designed for solid or stranded copper wire (strip ends to
7.9mm [5/16”]). Use 7 - 8 lb.-in. of torque to tighten the terminal clamps. Wire
size: (1) #18 AWG (.75mm

2

) minimum to (2) #12 AWG (14.0mm

2

)

maximum.

Wiring

Make connections as shown in Figure 3. Power is applied continuously to
terminals L1 and L2. Voltage applied and removed at initiating terminal P will
operate the instantaneous contacts and initiate timing as indicated in Table 1.

Use insulated copper wire rated at 75

°

C (167

°

F) or higher.

Operating

Mode

Power

(Terminals

L1-L2)

Voltage

(Applied to

Initiate

Terminal P)

Timer Status

Red LED

Indicator

Contact Cartridge Statue

Instantaneous

Timed

N.O

N.C

N.O

N.C

On-delay

On

No

Reset

Off

Open

Closed

Open

Closed

Yes

Timing

Flashing

Closed

Open

Open

Closed

Yes

Timed Out

On

Closed

Open

Closed

Open

Off

No

Stable

Off

Open

Closed

Open

Closed

Yes

Stable

Off

Closed

Open

Open

Closed

Off-delay

On

Yes

Reset

On

Closed

Open

Closed

Open

No

Timing

Flashing

Open

Closed

Closed

Open

No

Timed Out

Off

Open

Closed

Open

Closed

Off

No

Stable

Off

Open

Closed

Open

Closed

Yes

Stable

Off

Closed

Open

Open

Closed