Jumper installation, removal and storage, Drive identification – Rockwell Automation 20G PowerFlex 750-Series Power Jumpers User Manual

Page 4

Advertising
background image

4

Rockwell Automation Publication 750-IN011E-EN-P - February 2014

PowerFlex 750-Series Power Jumpers

Jumper Installation,
Removal and Storage

Jumper screws (Frames 2…5),
wires (Frames 1, 6 & 7) or plugs
(Frames 8…10) are used to
complete an electrical
connection when installed/
connected. When power jumper
screws are not used, they are
stored on the left interior chassis
wall as shown.

When installing a jumper screw or wire, note the recommended torque listed.

Drive Identification

The “Voltage Code” and “Default
Power Jumper Configuration” are
on the drive nameplate. Use this
information to perform the
proper procedure in the following
tables.

ATTENTION: Hazard of equipment damage exists if jumpers are not properly
disconnected.

For Frames 2…5, completely remove the jumper screw from the circuit board.

Frames 1, 6 & 7, secure the disconnected jumper wire to the standoff provided.

Frames 8…10 drive assemblies, secure the disconnected jumper plug in the socket
provided and ensure that all drive assemblies are identically configured.

Frames

Recommended Torque

Recommended Screwdriver/Socket

1

Not Applicable

Not Applicable

2…5

1.36 N•m (12.0 lb•in)

±0.14 N•m (1.2 lb•in)

6.4 mm (0.25 in.) flat or T15 Hexalobular

6…7

1.36 N•m (12.0 lb•in)

7 mm socket or T20 Hexalobular

Drive Power Jumpers

Frame 4 Shown

Jumper Screws
Installed

Jumper Screws Not
Installed

Jumper Screw Storage

Cat No. 20G11 N

D

011

A

A0NNNNN

UL Type 1 - only with Debris Hood and Conduit Plate

UL Open Type/IP20 - without Debris Hood and Conduit Plate

Specifications and Custom Catalog Number
representing options installed at factory.
See Nameplate 2 (Located behind HIM)
for equivalent base catalog number and separate options

Nameplate 1:

Mfd. in 2009 on Jan. 19

Series: A

Input: 3 Phase, 47-63Hz
AC Voltage Range
Amps ND (HD)

Power ND (HD)

Output: 3 Phase, 0-400 Hz
AC Voltage Range
Base Frequency (default)
Continuous Amps ND (HD)
60Sec Ovld Amps ND (HD)
3 Sec Ovld Amps ND (HD)

0-400
50 Hz

342-440

432-528

0-460
60 Hz

xxx
xxx
xxx

xxx
xxx
xxx

xxx
xxx
xxx

xxx
xxx
xxx

xxx

xxx

xxx

xxx

5.5 HP (4 HP)

7.5 HP (5 HP)

N223

Serial Number: xxxxxxxx

Original Firmware: x.xxx

TUV

Rheinland

Product Safety

.

.

Production inspected

W

E

C

EN 61800-5-1

Made in the U.S.A. Fac1C

400V Class

480V Class

II (2) G D

Functional Safety

Type approved

Voltage Code

Default Power Jumper Configuration