Rockwell Automation 20G PowerFlex 750-Series Power Jumpers User Manual

Page 6

Advertising
background image

6

Rockwell Automation Publication 750-IN011E-EN-P - February 2014

PowerFlex 750-Series Power Jumpers

5

C

D

E

PE-A Installed
PE-B Not Installed

PE-A Installed
PE-B Installed

Solid Ground
Install jumper screws at “PE-A” (MOV/Input Filter
Cap) and “PE-B” (CM Cap).
See

page 4

for recommended torque.

Non-Solid Ground
Remove both jumper screws.

6

C

D

E
F

PE-A jumper wire
connected to ground.
PE-B jumper wire
insulated/
disconnected from
ground.

PE-A jumper wire
and PE-B jumper
wire connected to
ground.

Solid Ground
Connect the MOV/Input Filter Cap jumper wire (PE-
A) and the CM Cap jumper wire (PE-B) to ground.
See

page 4

for recommended torque.

Non-Solid Ground
Insulat the MOV/Input Filter Cap jumper wire (PE-
A) and the CM Cap jumper wire (PE-B) from
ground.

7

C

D

E
F

PE-A jumper wire
connected to ground.
PE-B jumper wire
insulated/
disconnected from
ground.

PE-A jumper wire
and PE-B jumper
wire connected to
ground.

Solid Ground
Connect the MOV/Input Filter Cap jumper wire (PE-
A) and the CM Cap jumper wire (PE-B) to ground.
See

page 4

for recommended torque.

Non-Solid Ground
Insulate the MOV/Input Filter Cap jumper wire (PE-
A) and the CM Cap jumper wire (PE-B) from
ground.

Frame

Vo

lt

ag

e

Co

de

Factory Default Jumper Settings

Power Source Type

Catalog Code “A”

Catalog Code “J”

PE-B

PE-A

DC+

PE-B

PE-A

E4

Insulated

Connected

Insulated

Connected

PE-B

PE-A

Insulated

Connected

Insulated

Connected