Rockwell Automation 150 MNL/SMC DIALOG+/APP-PROD GUIDE User Manual
Page 24

SMC-2 Smart Motor Controller
2-5
Figure 2.6 SMC-2 Current Limit Selection
Table 2.D Rotary Position % Current Limit
Table 2.E
Current Limit Start Time
Table 2.F
Soft Stop (Available only with interface option)
Current Limit Level
Time Select
Starting Time
OFF Position
Starting Time
Starting Time
Soft Stopping Time (Active
only with interface option)
Soft Stopping Time (Active
only with interface option)
Soft Stopping Time (Active
only with interface option)
Current Limit
Energy Saver Select
(ON OFF)
/
50/60 H
(ON/OFF)
Auxiliary Contact (Up-to-Speed./Instant.)
(Active only with interface option)
ON Positio
Stall Select
(ON/OFF)
Soft Stop Select
(Active only with interface option)
Must be OFF when Soft Stop not used
Soft Stop Selec
(Active only with interface option)
Must be OFF when Soft Stop not used
NOTE: The switches shown above are for a 15 second, 300 percent
current limit start with a 25 sec o n d s o f t s t o p
Position
0
1
2
3
4
5
6
7
8
9
% of Full
Load Amps
25
50
100
200
250
300
350
450
500
550
Switch
Number
Time (seconds)
15
30
15
Off
On
14
Off
Off
13
Off
Off
Switch
Number
Time (seconds)
5
10
15
25
35
45
55
110
12
Off
On
Off
On
Off
On
Off
On
11
Off
Off
On
On
Off
Off
On
On
10
Off
Off
Off
Off
On
On
On
On