Rockwell Automation 150 MNL/SMC DIALOG+/APP-PROD GUIDE User Manual

Page 24

Advertising
background image

SMC-2 Smart Motor Controller

2-5

Figure 2.6 SMC-2 Current Limit Selection

Table 2.D Rotary Position % Current Limit

Table 2.E

Current Limit Start Time

Table 2.F

Soft Stop (Available only with interface option)

Current Limit Level

Time Select

Starting Time

OFF Position

Starting Time

Starting Time

Soft Stopping Time (Active
only with interface option)
Soft Stopping Time (Active
only with interface option)

Soft Stopping Time (Active
only with interface option)

Current Limit

Energy Saver Select
(ON OFF)

/

50/60 H
(ON/OFF)

Auxiliary Contact (Up-to-Speed./Instant.)
(Active only with interface option)

ON Positio

Stall Select
(ON/OFF)

Soft Stop Select
(Active only with interface option)
Must be OFF when Soft Stop not used

Soft Stop Selec
(Active only with interface option)
Must be OFF when Soft Stop not used

NOTE: The switches shown above are for a 15 second, 300 percent
current limit start with a 25 sec o n d s o f t s t o p

Position

0

1

2

3

4

5

6

7

8

9

% of Full

Load Amps

25

50

100

200

250

300

350

450

500

550

Switch

Number

Time (seconds)

15

30

15

Off

On

14

Off

Off

13

Off

Off

Switch

Number

Time (seconds)

5

10

15

25

35

45

55

110

12

Off

On

Off

On

Off

On

Off

On

11

Off

Off

On

On

Off

Off

On

On

10

Off

Off

Off

Off

On

On

On

On