Current limit start, Dual ramp start – Rockwell Automation 150 MNL/SMC DIALOG+/APP-PROD GUIDE User Manual

Page 40

Advertising
background image

SMC Dialog Plus Smart Motor Controller

3-3

Current Limit Start

This starting method provides a fixed reduced voltage start and is
used when it is necessary to limit the maximum starting current. Th
starting current is user adjustable from 50 to 600% of full load
amperes. The current limit starting time is user adjustable from 0 to
30 seconds.

Figure 3.3 Current Limit Start

Dual Ramp Start

This starting method is useful on applications with varying loads and
varying starting torque requirements. Dual Ramp Start offers the user
the ability to select between two separate Soft Start profiles with
separately adjustable ramp times and initial torque settings.

Figure 3.4 Dual Ramp Start

Start

600%

50%

Percent

Full Load

Current

Time (seconds)

Percent

Voltage

Initial

Torque #1

100

Start #1

Run #1

Ramp #2

Ramp #1

Start #2

Time (seconds)

Run #2

Initial

Torque #2