Programming - soft start with accu-stop (cont.) – Rockwell Automation 150 MNL/SMC DIALOG+/APP-PROD GUIDE User Manual
Page 76

SMC Dialog Plus Smart Motor Controller
3-39
Programming - Soft Start with Accu-Stop (cont.)
Parameter
Range
Slow Running Cur
This parameter allows the user to program the
Preset Slow Speed running current.
0 to 450% of full load current
Brake to Stop
This parameter allows the user to program
the controller to brake from full speed to zero
speed.
No, Yes
Braking Current
Allows the user to program the percentage of
braking current applied to the motor during the
stop sequence. With the SMC Smart Motor
Braking option, this is the current applied to
bring the motor to zero speed.
0 to 450% full load current
Stopping Current
Allows the user to program the percentage of
braking current applied to bring the motor from
Preset Slow Speed to zero speed.
0 to 400% of full load current
Parameter Mgmt
The newly programmed parameters values can
be saved to memory or the factory default
parameter values can be recalled.
Ready, Default Init., Recll Frm EE,
Store In EE