Interconnect drawings, Objectives, Des interconnect drawing – Rockwell Automation 1391 USER MNL/DIGITAL AC SERVO DR User Manual

Page 111

Advertising
background image

B

Appendix

B-1

Interconnect Drawings

Objectives

Appendix B provides typical interconnection diagrams that illustrate the
wiring between the 1391-DES and various other Allen-Bradley position
control products. Due to the numerous electrical circuit designs possible,
these diagrams are provided for reference only. The diagrams provided
include:

- 1391-DES interconnect drawing showing the inputs, outputs and

recommended control circuitry.

- 1391-DES / IMC 110 Interconnect Drawing

- 1391-DES / IMC 120 Interconnect Drawing

- 1391-DES / IMC 121, 123 and 123CR Interconnect Drawing

- 1391-DES / MAX CONTROL Interconnect Drawing

- 1391-DES / S (20x) Class Interconnect Drawing

- 1391-DES / S (21x) Class Interconnect Drawing

- 1391-DES / IMC-201 Interconnect Drawing

- 1391-DES / 9/Series Interconnect Drawing

1391-DES Interconnect Drawing

The 1391-DES Interconnect Drawing is presented on pages B-2 and B-3.
Refer to the “Notes” listed below when using this drawing.

Notes:

1) Power Wiring unless Noted:

15A

12 AWG (2.5 mm

2

) min. 75 degrees C min.

22.5A

10 AWG (4 mm

2

) min. 75 degrees C min.

45A

8 AWG (6 mm

2

) min. 75 degrees C min.

2) Signal Wiring: 18 AWG (0.75 mm

2

) min.

3) Allen-Bradley Supplied Cable:

8 AWG (6 mm

2

) Motor

126473

12 AWG (2.5 mm

2

) Motor

126474

Resolver

116190

4) Customer Supplied Resolver Cable:

Belden 9873 or equivalent, 20 AWG (0.5 mm

2

), 30 pf/ft (97.5 pf/m) max. capacitance between

conductors.

5) Terminate shield on source end only.

6) Do not make connections to unused pins on the resolver connector.

7) F3 provided on 15 & 22.5A units only. 15A=KLM-10, 22.5A=FNQ 6 1/4.

8) Parameter 130 must be set to zero in this configuration.

9) Apply either +5V DC to TB3-7 or 8-15V DC to TB3-9 (do not apply both).

10) NC = No connection.

Advertising