Rockwell Automation 1391 USER MNL/DIGITAL AC SERVO DR User Manual

Page 90

Advertising
background image

Chapter 10
Transformers and Shunt Regulators

10-2

Figure 10.1
1391 Transformer Wiring Diagrams

1

H6

H7

H8

H9

H10

H1

H2

H3

H4

H5

H11 H12 H13 H14 H15

P1

P2

G1 G0

Y1

Y2

36V AC

CT 200VA

Y3

Y4

Y5

36V AC

CT 200VA

Y6

Y7

Y8

36V AC

CT 200VA

Y9

Y10

Y11

36V AC

CT 200VA

Y12

Faraday

Shield

230V AC

230V AC

230V AC

X0

Thermal switch for transformer protection
(rated 115V AC, 1A, 24V DC/0.25A min.,

H1

H3 H2

H4

P1

P2

G0

Y1

Y2

36V AC

CT 200VA

Y3

Y4

Y5

36V AC

CT 200VA

Y6

Y7

Y8

36V AC

CT 200VA

Y9

Y10

Y11

36V AC

CT 200VA

Y12

Faraday

Shield

230V AC

230V AC

230V AC

X0

Thermal switch for transformer protection
(rated 115V AC/1A, 24V DC/0.25A min.,

H6 H5

H7

H9 H8

G1

G2

X1

X2

X3

Primary
Voltage

240V AC

380V AC

415V AC

480V AC

Connect

H2 to H6
H7 to H11
H12 to H1

H3 to H6
H8 to H11
H13 to H1

H4 to H6
H9 to H11
H14 to H1

H5 to H6
H10 to H11
H15 to H1

Lines On

H1
H6
H11

1391–TxxxET (50/60 Hz.)

X1

X2

X3

Primary
Voltage

208V AC

240V AC

480V AC

575V AC

Connect

H2 to H6
H7 to H11
H12 to H1

H3 to H6
H8 to H11
H13 to H1

H4 to H6
H9 to H11
H14 to H1

H5 to H6
H10 to H11
H15 to H1

Lines On

H1
H6
H11

1391–TxxxNT (60 Hz.)

Primary
Voltage

240V AC

480V AC

Connect

H1 to H3 to H8
H2 to H4 to H6
H5 to H7 to H9

H2 to H3
H5 to H6
H8 to H9

Lines On

H1
H4
H7

H1
H4
H7

1391–TxxxDT (60 Hz.)

185

_C

±

5

_C

185

_C

±

5

_C)

1

The Y2, Y5,Y8 and Y11 center taps are available but not used with the 1391-DES.

Advertising