Rockwell Automation 1608M MegaDySC User Manual, 208 Volt, One Second Extended Runt User Manual

Page 43

Advertising
background image

43

Rockwell Automation Publication 1608M-UM004A-EN-P - April 2014

Chapter 7

Maintenance

33

UNBALANCE

Start-Up Test: DC Bus Unbalance

Call Service

Inverter

Positive and negative halves of the DC
bus did not charge equally during power
up.

Call service.

34

AC_V_CHK

Start-Up Test: AC Voltage Check

Call Service

Inverter

Output voltage was detected out of
tolerance during the start-up test.

Call service.

35

ROLL_CALL

Start-Up Test: Controller Roll Call
Timeout

Call Service

Unit

Controller communication problem
detected during start-up test.

Call service.

36

COM_VER

Start-Up Test: Communication
Compatibility Mismatch

Call Service

Unit

Firmware communication compatibility
problem detected during start-up test.

Call service.

37

CNFG_TO

Start-Up Test: Controller Configuration
Timeout

Call Service

Unit

Controller communication problem
detected during start-up test.

Call service.

38

CNFG_ERR

Start-Up Test: Controller Configuration
Mismatch

Call Service

Unit

Controller firmware configuration
problem detected during start-up test.

Call service.

39

FIRM_TO

Start-Up Test: Controller Firmware
Check Timeout

Call Service

Unit

Controller communication problem
detected during start-up test.

Call service.

40

FIRM_DIFF

Start-Up Test: Controller Firmware
Revision Mismatch

Call Service

Unit

Controller firmware revision mismatch
detected during start-up test.

Call service.

41

SRL_TO

Start-Up Test: Controller Serial Number
Check Timeout

Call Service

Unit

Controller communication problem
detected during start-up test.

Call service.

42

SRL_DIFF

Start-Up Test: Serial Number Mismatch

Informational

Unit

Controller serial number mismatch
detected during start-up test.

No action needed.

44

T_INV_TO

Inverter Test Timeout

Call Service

Unit

Phase control board failed to respond to
Comm board's Inverter test.

Call service.

46

DOOR_OPEN

DySC Cabinet Door Open

Manual Reset

Unit

DySC door was opened. Mechanical
bypass commanded.

Close door. Manually reset DySC.

47

CRIT_OT

Critical Over-Temperature

Manual Reset

Unit

Internal DySC temperature exceeded
maximum rating. Mechanical bypass
commanded.

Verify ambient temperature is within DySC
specification. Check for damaged fans. Check for
dirty or obstructed air filters. Manually reset DySC.

48

FUSE_OPEN

Fuse Open

Call Service

Unit

One of the DySC fuses was detected
open. Mechanical bypass commanded.

Call service.

49

OPEN_SCR_A

Open SCR Phase A

Call Service

Static
Switch

The SCR on the phase A module was
detected open.

Call service.

50

OPEN_SCR_B

Open SCR Phase B

Call Service

Static
Switch

The SCR on the phase B module was
detected open.

Call service.

51

OPEN_SCR_C

Open SCR Phase C

Call Service

Static
Switch

The SCR on the phase C module was
detected open.

Call service.

52

EXT_MB

External Mechanical Bypass Command

Manual Reset

Unit

The DySC was externally commanded to
transfer to mechanical bypass.

Manually reset DySC.

53

DYN_BRAKE

Dynamic Brake Error

Call Service

Unit

A problem was detected with the DySC
dynamic brake controller.

Call service.

58

PLC_ERR

Programmable Logic Controller Error

Call Service

PLC

PLC error detected.

Call service.

59

PLC_ST_MM

Programmable Logic Control State Mismatch

Call Service

Unit

PLC feedback error detected.

Call service.

Event Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution