Setup, Continued) j14 – Rockwell Automation 1397-L11 I/O Expansion Card User Manual

Page 10

Advertising
background image

10

1397 I/O Expansion Card

1397 – 5.19 August, 2000

Analog Output Settings

The I/O Expansion Card supports two analog outputs — Anlg Out 3
and Anlg Out 4. Both I/O Expansion Card outputs are unfiltered,
where as standard analog outputs are averaged.

Anlg Out 3 has (2) parameter settings

1

and can be jumpered to supply

(2) types of output signals.

Anlg Out 4 has (2) parameter settings

1

and can only supply a bipolar

DC voltage.

Analog outputs can be scaled to supply DC voltage signals as low as
5V DC, but the maximum resolution of 0.025% is only obtained when
a full scale output signal is used. Analog outputs are updated every
20mS.

Parameter No.

Parameter Name

Terminal Nos.

P.151

Anlg Out 3 SRC

54 and 55

2, 3, 4, 5

P.150

Anlg Out 3 Gain

P.154

Anlg Out 4 SRC

56 and 57

1

P.153

Anlg Out 4 Gain

1

For a detailed description of these Analog Output Parameters, refer to the parameter
descriptions in the 1397 User manual.

53

54 55

56

57

59

60

61

62

58

J6

Anlg Out 3

Anlg Out 4 +

Anlg Out 4

Anlg Out 3 +

Setup

(continued)

J14

Set f

or

Volts

ANALOG

OUTPUT 1

V

2

For A Bipolar DC Output Voltage — Set analog output jumper J14 to V.

J14

Set f

or

Amps

J15

Set f

or

4-20mA Output

Internal Sour

ce

ANALOG

OUTPUT 1

M

A

IOUT

SOURCE

IN

T

3

For A 4-20mA Output Internal Source — Set analog output jumpers J14 to mA and J15 to INT.

J14

Set f

or

Amps

J15

Set f

or

4-20mA Output

External Sour

ce

ANALOG

OUTPUT 1

MA

IOUT

SOURCE

EX

T

4

— Set analog output jumpers J14 to mA and J15 to EXT.