Setup – Rockwell Automation 1397-L11 I/O Expansion Card User Manual

Page 11

Advertising
background image

1397 – 5.19 August, 2000

1397 I/O Expansion Card

11

Setup

(continued)

Frequency Input Setting

To configure the I/O Expansion Card’s single unipolar frequency
input, only parameters

1

must be set. The frequency input signal is

read every 20mS.

Parameter No.

Parameter Name

Terminal Nos.

P.011

Frequency In

39, 40 and 41

P.138

Freq In Zero

P.137

Freq In Scale

38

39 40

41

42

44

50

51

52

43

J5

Freq In A

Com

Freq In A

Frequency Output Setting

To configure the I/O Expansion Card’s single unipolar frequency
output, only parameters

1

must be set. The output signal is unfiltered

and read every 20mS. The full scale value is based on their selected
parameter group — Load, Speed, Voltage, Power, Field or other.

Parameter No.

Parameter Name

Terminal Nos.

P.160

Freq Out SRC

42, 43 and 44

P.161

Freq Out Zero

P.159

Freq Out Scale

38

39 40

41

42

44

50

51

52

43

J5

Freq Out A

Com

Freq Out A

5

Wiring an external supply for 4-20mA output.

Shield to

Chassis

Ground Stud

I/O
TB J6

Load

(1.3k

Max.)

External Voltage

(+32V

DC Max.)

+

54 Anlg Out 3 +

55 Anlg Out 3 –

4-20mA Output

1

For a detailed description of these Frequency I/O Parameters, refer to the parameter descriptions
in the 1397 User manual.