Startup
Chapter 6
6-14
Final Settings
Step 24
- Motor Connected
If Heavy Duty Dynamic Braking is to be Installed
- Load Connected
If Heavy Duty Dynamic braking is required, set Parameters 11 and 14 to 0.
Step 25
If Machine Resonance is Encountered
Set Parameters 42-45 to skip those frequencies which cause the machine to
resonate.
Step 26
If Nuisance Tripping is Encountered
Enable Parameters 17 and/or 18 to disable drive acceleration or
deceleration during high Bus current or voltage conditions.
Step 27
If the Connected Load is an Overhauling Load
Set Parameter 18 to 0 to disable Decel Frequency Hold.
Step 28
If a Different Running Monitor Mode is Required
Change Parameter 57 to:
•
0 to monitor drive output current.
•
1 to monitor equivalent motor RPM.
•
2 to monitor drive control frequency.
Step 29
If an External 2 or 3-Wire Control Scheme is to be Used
•
Connect the 2 or 3-wire controls as shown in Figure 4-3 and described in
Chapter 4.
•
Set Parameter 8 to 1 for 2-wire control, 3 for 3-wire control.
•
Repeat the startup procedure starting from step 1.