Preset frequency settings – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 75

Operation and Programming
Chapter 5
5-32
Preset Frequency Settings
Auxiliary Preset Frequencies are enabled or disabled by Parameters 19 and
20. Individual Preset Frequency settings are selected by setting switches
S1, S2 and/or S3 as shown in Parameters 19 and 20.
Parameter
29
-- Preset Frequency 2
Units
= Hertz
Range
= 00.50/400.0
Factory Setting = 20.00
From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 2
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 2
in 0.1 Hz increments.
Parameter
30
-- Preset Frequency 3
Units
= Hertz
Range
= 00.50/400.0
Factory Setting = 30.00
From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 3
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 3
in 0.1 Hz increments.
Parameter
31
-- Preset Frequency 4
Units
= Hertz
Range
= 00.50/400.0
Factory Setting = 40.00
From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 4
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 4
in 0.1 Hz increments.