Ladder program description continued – Rockwell Automation 1402-LSM Line Synchronization Module Installation Instructions User Manual

Page 45

Advertising
background image

Chapter 4
Application Information

4–11

Data Files Used Continued

Table 4.5

File

Description

N30

Factory Configuration Parameters BTR Destination

N31

User Configuration Parameters BTR Destination

N32

Acknowledge Factory Configuration Parameters BTR Destination

N33

Acknowledge User Configuration Parameters BTR Destination

N34

Synchronizing Bus Error Parameters BTR Destination

N35

Synchronizing Bus Voltage/Current Parameters BTR Destination

N36

Synchronizing Bus Power Parameters BTR Destination

N37

Reference Bus Voltage Parameters BTR Destination

N38

Diagnostic Parameters BTR Destination

N39

Factory Configuration Parameters BTW Source

N40

User Configuration Parameters BTW Source

N41

Control Request BTW Source

R6:0

Sequencer Control–Configuration

R6:1

Sequencer Control–Run

I

Discrete Inputs to the PLC–5

O

Discrete Outputs from the PLC–5

Accessing BTR Data from PLC Ladder

To access a specific parameter from any of the BTRs, the BTR destination
file must be known as well as the parameter number of the parameter desired.
An illustration of this is an example taken directly from the Block Transfer
Tables document and the example ladder diagram. (See Appendix B & C).

To obtain Synchronizing Bus Frequency in Hz from the Synchronizing Bus
Voltage/Current Parameters BTR, the following words need to be read:
N35:37 and N35:38.

Since the frequency is divided in 10

0

and 10

-3

formats, the following

operations need to be performed to create a floating point representation of
this number:

(N35:37

/1000) +

N35:38

=

frequency in floating point

For display purposes on a panel view terminal for example, it may not be
necessary to perform this operation if the data can be divided into two fields
and displayed as follows: N35:38. N35:37.

Ladder Program Description
Continued