Table B.8
Synchronizing Bus
Power Parameters
Parameter
Number
Word
Number
Description
Range
Modulus
1
1
Power Factor in Percent – Total
±
0 – 100
10
0
2
2
Power Factor in Percent – (L1–N)
±
0 – 100
10
0
3
3
Power Factor in Percent – (L2–N)
±
0 – 100
10
0
4
4
Power Factor in Percent – (L3–N)
±
0 – 100
10
0
5
±
0 – 999
10
0
5
6
Power in Watts – Total
±
0 – 999
10
3
7
±
0 – 999
10
6
8
±
0 – 999
10
0
6
9
Power in Watts – (L1–N)
±
0 – 999
10
3
10
1
±
0 – 999
10
6
11
±
0 – 999
10
0
7
12
Power in Watts – (L2–N)
±
0 – 999
10
3
7
13
2
±
0 – 999
10
6
14
±
0 – 999
10
0
8
15
Power in Watts – (L3–N)
±
0 – 999
10
3
16
3
±
0 – 999
10
6
17
±
0 – 999
10
0
9
18
Apparent Power in VA – Total
±
0 – 999
10
3
9
19
V
±
0 – 999
10
6
20
±
0 – 999
10
0
10
21
Apparent Power in VA – (L1–N)
±
0 – 999
10
3
1
22
V
1
±
0 – 999
10
6
23
±
0 – 999
10
0
11
24
Apparent Power in VA – (L2–N)
±
0 – 999
10
3
11
25
V
2
±
0 – 999
10
6
26
±
0 – 999
10
0
12
27
Apparent Power in VA – (L3–N)
±
0 – 999
10
3
12
28
V
3
±
0 – 999
10
6
29
±
0 – 999
10
0
13
30
Reactive Power in VAR – Total
±
0 – 999
10
3
13
31
V
±
0 – 999
10
6
32
±
0 – 999
10
0
14
33
Reactive Power in VAR – (L1–N)
±
0 – 999
10
3
14
34
V
1
±
0 – 999
10
6