Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual

Page 146

Advertising
background image

Table of Contents

8–51

Parameter 593 – [A>ChB DH Rd Nde4]
Parameter 543 – [B>ChB DH Rd Nde4]

Use: Channel B Read Station Number 4
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 77
Default Value: 8

Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter specifies which node address the
DH TP In 4 parameter will receive its data from. The node address is
entered in octal so that it corresponds with the node addressing scheme of
DH+. The default value of 8 disables the data transfer.

Parameter 594 – [A>ChB DH Rd Wrd4]
Parameter 544 – [B>ChB DH Rd Wrd4]

Use: Channel B Read word 4
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 1
Default Value: 0

Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter determines which of these two
words the DH TP In 4 parameter will receive its data from. The node
address is specified by the DH Rd Nde4 parameter.

Parameter 588 – [A>Redund Chan No]
Parameter 538 – [B>Redund Chan No]

Use: Specifies RIO Redundant Channel Number
Parameter Type: Configuration
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 1
Default Value:
0

Description: This parameter determines which channel number will be
used by the Drive for control purposes. Data and messages from the
selected channel will be passed to the Drive.Data and messages from the
other channel will be discarded. The choices are:
0 = Channel A
1 = Channel B