Figure 3-21. PLC5/15 - 1395 DC Drive Sample Program cont.
Rung 2:2
B3
Drive 1
Parameter
Write
This rung will write to parameters 500 – 999 in the drive when bit B3/1 is toggled from a zero to a one. The parameter
values to be sent to the drive are stored in N30: 0 – 499.
Enable
Message
Read
From
Drive 1
1
MSG
SEND/REC MESSAGE
Control Block N7: 20
(EN)
(DN)
(ER)
Communication Command:
PLC–5 Data Table Address:
Size in Elements:
Local/Remote:
Remote Station:
Link ID:
Remote Link Type
Local Node Adress:
Destination Data Table Address:
PLC–5 TYPED WRITE
N30:0
500
LOCAL
N/A
N/A
N/A
11
N10: 500
ignore if timed-out:
to be retried:
awaiting execution:
continuous:
error:
message done:
message transmitting
message enabled:
0 TO
0 NR
0 EW
0 CO
0 ER
0 DN
0 ST
0 EN
MESSAGE INSTRUCTION DATA MONITOR FOR CONTROL BLOCK N7:20
control bit addr: N7: 20/15
ERROR CODE: 0 (DEC)
BLOCK SIZE = 10 WORDS
Press a function key to change a value.
>
Rem Prog Forces: None Data: Formatted