Selection of Cables

Table 4 - DC Input/Output Wiring for External Battery Cabinet

Connect 1609-EXBAT
to the UPS

To install the 1609-EXBAT unit with the 1609-D UPS, connect the three 10
AWG wires from the 1609-EXBAT terminals to the 1609-D UPS terminals
marked as ‘EXTERNAL BATT PACK (36V)’. (See Figure 8)

Dispose of used batteries according to the battery instructions.

Figure 8 - System Wiring

Item Specification

Wire Size

10 AWG

Minimum temperature

75 °C

Wire conductor material

Copper only

Tightening torque for terminals

12 lb-in.