Rockwell Automation 1609-B_D UPS Product User Manual User Manual

Page 24

Advertising
background image

24

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

Bulletin 1609 UPS

8

Over Voltage from The Output
of AVR

The UPS has detected an
over voltage on the output
of AVR and disabled its
output.

Have qualified electrician verify that the quality of the output voltage and the input utility voltage are
within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists,
contact Technical Support.

9

Under Voltage from The Output
of AVR

The UPS has detected low
voltage on the output of
AVR and disabled its
output.

Have qualified electrician verify that the quality of the output voltage and the input utility voltage are
within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists,
contact Technical Support.

10

Fan Failure

The UPS has detected that
the fan of the UPS has
failed and disabled its
output.

To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists,
contact Technical Support.

11

Charger Failure

The UPS has detected that
the battery charger circuit
has failed; however, the
UPS will continue running.

Clear this fault by removing the input utility voltage and batteries then plug the batteries back in place
and turn the input utility voltage back on. Enable the UPS output to verify the fault.
If the Charger Failure persists, contact Technical Support.

12

TMOV Failure

The UPS has detected that
the MOV circuit has failed;
however, the UPS will
continue enabling the
output.

Schedule to have a qualified electrician replace the MOV board (1609-SPD).
Remove the input utility power before service on this 1609-SPD due to risk of electrical shock.

13

Missing Battery

The UPS has detected that
the batteries are missing;
however, the UPS will
continue enabling the
output.

Have a qualified electrician verify the battery connection for good contact and charge the batteries for
24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
indicates Missing Battery, new batteries are required.

14

Replace Batteries

The UPS has detected that
the batteries are bad;
however, the UPS will
continue running.

Have a qualified electrician verify the battery connection for good contact and charge the batteries for
24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
indicates Replace Battery, new batteries are required.

No.

Fault

Description

Solution

BLINK

GRN

RED

BLINK

GRN

RED

GRN

RED

BLINK

GRN

GRN

BLINK

GRN

GRN

BLINK
RED

GRN

GRN

RED