Factory-default settings -3 quick configuration -3, Factory-default settings, Quick configuration – Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual

Page 19

Advertising
background image

Configuring the Module

2–3

Factory-Default Settings

The module is shipped with the following settings:

Quick Configuration

For detailed switch information, refer to pages 2–4 through 2–13.

Feature

Switch(es) Default Setting

Block Transfer

3.1

Enabled

Logic Command/Status

3.2

Enabled

Reference/Feedback

3.3

Enabled

Datalinks

3.4 – 3.7

Datalinks A and B are Enabled
Datalinks C and D are Disabled

Truncate Last Datalink

3.8

Disabled

Starting Group

2.1 – 2.2

0

Last Rack

2.3

Not Last Rack

Fault Action

2.4 – 2.6

Fault on communications loss
Hold last state on reset/program/test

Baud Rate

2.7 – 2.8

57.6K

Not Used

1.1 – 1.2

Not Used

Rack Address

1.3 – 1.8

2

Switch

Setting Description

3.1

0
1

Disable block transfer
Enable block transfer

3.2

0
1

Disable Logic Command/Status
Enable Logic Command/Status

3.3

0
1

Disable Reference/Feedback
Enable Reference/Feedback

3.4

0
1

Disable Datalink A (A1 and A2)
Enable Datalink A (A1 and A2)

3.5

0
1

Disable Datalink B (B1 and B2)
Enable Datalink B (B1 and B2)

3.6

0
1

Disable Datalink C (C1 and C2)
Enable Datalink C (C1 and C2)

3.7

0
1

Disable Datalink D (D1 and D2)
Enable Datalink D (D1 and D2)

3.8

0
1

Disable truncate last datalink
Enable truncate last datalink

2.1 – 2.2 2.2

1
0
1
0

2.1

1
1
0
0

Starting group 0
Starting group 2
Starting group 4
Starting group 6

2.3

0
1

Not last rack
Last rack with this address

2.4

0
1

Hold last state
Zero data

2.5

0
1

No fault. Use action of switch 2.4
Fault drive on communications loss

2.6

0
1

No fault. Use action of switch 2.4
Fault drive on Reset/Program/Test

2.7 – 2.8 2.8

0
0
1

2.7

0
1
0

57.6 kbps
115.2 kbps
230.4 kbps

1.1 – 1.2

Not Used

1.3 – 1.8 Varies

See “Setting the Rack Address” on
page 2-13

Off = 0
On = 1

Off = 0
On = 1

Off = 0
On = 1

Advertising