Connect the power supply to the module – Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual

Page 35

Advertising
background image

Installing the Module

3–5

5. If the module is the last device on the Remote I/O link, connect

the termination resistor. If the Remote I/O link uses 230Kbps,
you must use an 82 ohm termination resistor.

Figure 3.4

Connecting the Termination Resistor

6. Connect the power supply to the module.

Figure 3.5

Connecting the Power Supply

7. Apply power to the Remote I/O link. The module is now

installed. Its LEDs are as follows:

You are now ready to create a ladder logic program.

Important: If your LEDs are different, refer to Chapter 6.

Blue

Shield

Clear

To
Another Remote I/O
Link Device

1

2

I50 Ohm
or
82 Ohm
1 watt
+/-10%

Sh

GND

Hi 115V/230V AC

Low 115V/230V AC

GND

24V DC
Supply

-

+

L
N
G

+
-
G

1203-GD1 Module

1203-GK1 Module

LED

Status

Fault

Red (Blinking)

SCANport STS

Green or amber

➀ ➁

Health

Green or amber

Rem I/O ACT

Off

Rem I/O STS

Off

This LED is off if the module use firmware 2.xx or lower.

Early versions of the module use amber LEDs.