Scanport link connection – Rockwell Automation 1203 Serial Communications Module Series A User Manual

Page 32

Advertising
background image

Chapter 3
Installation

3-16

SCANport Link Connection

Cable Requirements

SCANport cables are available in either Male to Male or Male to Female
configuration. Cables of up to 10 meters (33 feet) can be connected from
the master to the SCANport device (A in Figure 3.9). If a Port Expander is
used as shown in Figure 3.9, the cable length from the master to the Port
Expander must be subtracted from the cable length used to connect the
device to the expander (B1 + C = max 10 meters).

1305 Drive

An Allen-Bradley SCANport link cable is used to make the connection
between the Communications Module and the drive (Figure 3.9).

Figure 3.9
SCANport Connection on Communications Module

1305 Drive

Human Interface

Module

Port 1

A

Port 2

Optional

Male–Female

Cable

Optional

Male–Male

Cable

B1

2

3

4

5

Port Expander

B2

C

Communication

Module

Communication

Module

AB0407B

IMPORTANT: The maximum cable distance between any two devices
cannot exceed 10 meters (33 feet) of cable.

For example: A + B1 + C

10 meters

A + B2 + C

10 meters

B1 + B2

10 meters

Advertising