Rockwell Automation 1203 Serial Communications Module Series A User Manual
Page 50

Chapter 6
Troubleshooting
6-2
ATTENTION: Do not attempt to defeat or override fault circuits.
The cause of a fault indication must be determined and corrected
before attempting operation. Failure to correct a drive or system
malfunction may result in personal injury and/or equipment
damage due to uncontrolled machine system operation.
Table 6.A
LED Troubleshooting Table
Indicator
Color
Description
Recommended Action
Serial Sts
Green (Blinking)
Link OK, off-line
Check configuration switch settings,
check for serial cable connection,
cycle Communications Module power
Green (Steady)
Link OK, on-line
None, system functioning properly
Red (Steady)
Faulted
Check configuration switch settings,
check for serial cable connection,
cycle power, replace module
SCANport Sts
Green (Blinking)
Link OK, not connected
Check configuration switch settings,
check for serial cable connection,
cycle power
Green (Steady)
Link OK, connected
None
Red (Steady)
Faulted
Check configuration switch settings,
check for serial cable connection,
cycle power, replace module
TX
Off
No transmission occurring
Send serial data again
Amber
Transmission occurring
None
RX
Off
No transmission received
Check data device to verify it is sending
data
Amber
Transmission being received
None