Rockwell Automation 931S-C4C5D-BC Active Converter User Manual

Page 8

Advertising
background image

8

3.6 Setting tool for all input and output values

Definitions:

In

min

= smallest input value

In

max

= largest input value

Out

min

= smallest output value

Out

max

= largest output value

OS = output span (take from table on Pg 22)
EV = upper end value (take from table on Pg 22)

1. Select output range of unit (according to table on Pg 22) so that Out

min

and Out

max

are within the output range.

2. Calculate the following auxiliary quantities:

3. Set all DIP switches to OFF.
4. Calculate input range IR, set output range and offset OF with DIP

switches.

4a. If the calculated offset OF does not correspond with an offset which can

be set with the DIP switches, set the closest offset (see table on page 22)
and activate the zero potentiometer (switch 2-5 OFF), short-circuit input
and adjust output to value Out

min

– (In

min

x F).

4b. If the calculated input range IR does not correspond with a range

which can be set with the DIP switches set the largest range within
0.33 x IR … 3.30 x IR (see table on page 21) and activate the span
potentiometer (switch 2-4 OFF), modulate input with value

0 (see table

on page 21 for terminals) and adjust output to required value (e.g. set
In

max

, adjust to Out

max

).

Input range

IR

OS

F