All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
17
Bulletin 1606 Switched Mode Power Supplies
25. Application Notes
25.1. Periodic Peak Power Capability
Fig. 26 Periodic peak power capability
The short term power can be used
periodically.
The duration of the peak power (Tp)
must be shorter than 15s.
The time between two peak power
pulses must be three times longer than
the duration of the preceding pulse
length.
t
T
100%
125%
P
OUT
P
NOM
T
P
> 3x T
P
25.2. Charging Batteries
Do not use this power supply to charge batteries.