All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

6

Rockwell Automation Publication 1606-RM024A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

7. Output

Output

voltage

nom.

24.1V

Output voltage adjustment range

none

The output voltage is fixed. No adjustment possible.

Output current

nom.

40A continuous,

see

Fig. 7-1

50A

up to 15s with full output voltage, see Fig. 7-1

Short-circuit current

typ.

180A

load impedance 25mOhm, see Fig. 7-1

Note: The short-circuit current is available for 0.1s.

Output

power

nom.

960W

continuous

1200W

up

to

15s

Line

regulation

max.

±2%

see

Fig. 5-1

Load

regulation

max.

800mV

static value, 0A 40A

0A

max.

200mV

static value, 5A 40A

5A

Ripple and noise voltage *)

max.

1500mVpp

20Hz-2kHz,

50Ohm

max.

50mVpp

2kHz to 20MHz, 50Ohm

Output

capacitance

typ.

20 000μF

*) The ripple and noise voltage mostly consist of a mains ripple with 300Hz (50Hz mains) or 360Hz (60Hz mains). The ripple and
noise voltage can be reduced by using external capacitors.

The power supply is also designed to support loads with a higher short-term current and power requirement. The
short-term duration is firmware-controlled by an output power manager. If the nominal output power is exceeded for
a certain period of time which is defined in zone A, B and C, the power supply responds with an automatic shut-
down. Pressing the reset button or cycling the input power (10s off time is required) initiates a restart attempt.
If the fault has been cleared the device will operate normally.
The short term power can be used periodically . See section 25.1 for further information.

Fig. 7-1 Output voltage vs. output current, typ.

V

OUT

40A

A

0

4

1

A

0

5

80A

0

A

15s

24V

200A

60A

A

0

8

1

A

0

6

1

A

0

2

1

A

0

0

1

A

0

2

12V

I

OUT

B

5s

C

0.1s

3x 408V
3x 480V
3x 552V

Zone A : 25% extra output power for typ. 15s

Zone B: 100% higher output current for typ. 5s

Zone C: Quick-acting shut-down after typ. 0.1s